Description
Configurations
Can be configured to use other fire fighting agents such as dry powder, CO2 or HFC227 depending on intended usage.
The activation temperature of the sprinkler bulb can be configured to 57°C / 68°C / 79°C / 93°C / 141°C
*Warning, if you are unsure which temperature to use, consult out fire protection experts first. Using the wrong configuration will prematurely activate the automatic fire extinguisher.
Classification | Activation Temp | Ambient Temp | Color |
Ordinary | 57°C | 38°C | Orange |
Ordinary | 68°C | 38°C | Red |
Intermediate | 79°C | 65°C | Yellow |
Intermediate | 93°C | 65°C | Green |
High | 141°C | 107°C | Blue |
Maintenance
This automatic fire extinguisher should be serviced at least once a year. It should be recharged immediately after any use. Recharging should be done by a qualified person. The cylinder body should be hydrostatic tested every 5 years or earlier if there are signs of damage.
Specifications
Capacity | 3KG | 5 KG |
Model | HFC-AUTO-3KG | HFC-AUTO-5KG |
Extinguishing Agent | HFC227EA | HFC227EA |
Propellant | Self propel | Self propel |
Activation Temp | 57 / 68 / 79 / 93 / 144°C | 57 / 68 / 79 / 93 / 144°C |
Working Pressure | 14 Bar | 14 Bar |
Operating Temp | -10°C to Activation Temp | -10°C to Activation Temp |
Test Pressure | 25 Bar | 25 Bar |
Part No | HFC-AUTO-3KG | HFC-AUTO-5KG |
*Due to constant improvements, product specifications may differ slightly.